S/FTP CAT 7A, 4-pair cable (100 Ohm) PiMF with each pair shielded with AL/Mylar tape and overall tinned copper braid, FR LSZH (Low Smoke Zero Halogen) flame and fire retardant jacket, tested up to 1 GHz. Ideal for the realization of transmission channels of Class FA.
|
|
Applications and performance |
Cable suitable for the realization of generic cabling systems according to EN 50173; ISO/IEC 11801.
Ideal for indoor applications in Class D, E, EA, F and FA over 10 GbE on IEEE 802.3an, PoE/PoE+/ PoE++ protocols. Electrical characteristics exceed Category 7A requirements.
|
|
Fire behaviour |
CPR regulation : Euroclass B2ca s1a, d1, a1 |
|
Reference standards
|
Data transmission cables of Category 7A according to ISO/IEC 11801; IEC 61156-5; EN 50173-1.
|
|
Construction characteristics
|
Inner conductors - material/diameter
|
Solid bare copper/AWG 23/1 (0,58mm)
|
Insulation - material/diameter
|
Foam skin PE max. diam. 1,35
|
Pair Shield
|
Al/Mylar tape
|
Overall shield
|
Tinned copper wire braid
|
Cable diameter
|
7,8 ± 0,5 mm
|
Outer jacket - material/color
|
LSZH/Yellow RAL 1021
|
Lead-free
|
Yes
|
Cable weight
|
63 kg/Km
|
|
|
ELECTRICAL CHARACTERISTICS ACCORDING TO FREQUENCY
|
Freq
|
Attenuation
|
NEXT
|
PS-NEXT
|
ACR
|
PS-ACR
|
ACR-F
|
RL
|
MHz
|
dB/100m
|
dB
|
dB
|
dB@100m
|
dB@100m
|
dB@100m
|
dB
|
|
max.*
|
Tip.
|
min.*
|
Typ.
|
min.*
|
Tip.
|
min.*
|
Typ.
|
min.*
|
Typ.
|
min.*
|
Typ.
|
min.*
|
Typ.
|
1
|
2.1
|
1.9
|
80
|
105
|
77
|
102
|
77.9
|
103
|
75
|
100
|
80
|
95
|
23
|
25
|
10
|
5.8
|
5.5
|
80
|
105
|
77
|
102
|
74.2
|
99.5
|
71.2
|
96.5
|
75
|
92
|
25
|
30
|
62.5
|
14.6
|
13 |
78 |
101 |
75.5 |
99 |
63.4 |
88 |
60.9 |
86 |
59.5 |
80 |
21.5 |
31 |
100
|
18.5
|
17.6 |
74 |
100 |
72.4 |
97 |
55.5 |
82.4 |
53.9 |
79.4 |
55.3 |
76 |
20.1 |
33
|
200
|
26.5
|
25.3 |
70.8 |
93 |
68 |
90 |
44.3 |
67.7 |
41.5 |
64.7 |
49.7 |
70 |
18 |
29 |
500
|
42.8 |
40.4
|
65 |
85 |
61.9 |
82 |
22.2 |
44.6 |
19.1 |
41.6 |
41.8 |
60 |
17.3 |
24 |
600
|
47.1
|
44.9 |
63.7 |
81 |
60.7 |
78 |
16.6 |
36.1 |
13.6 |
33.1 |
39.8 |
58 |
17.3 |
23 |
700
|
51.1 |
49 |
62.7 |
79
|
59.7 |
75
|
11.6 |
30 |
8.6 |
26 |
38.4 |
50
|
14.2 |
21 |
1000 |
61.9 |
58.5 |
60.4 |
74 |
57.4 |
71 |
-1.5 |
15.5 |
-4.5 |
12.5 |
35.3 |
43 |
13.1 |
19 |
|
* According to EN 50288-9-1, IEC 61156-5(2012)
|