F/UTP CAT6, 4-pair cable (100 Ohm) with cross separator, shielded with an Aluminim/Polyester tape, LSZH (Low Smoke Zero Halogen) flame retardant jacket, tested up to 500 MHz. Suitable for the realization of transmission channels of Class E.
Applications and performance
Cable suitable for the realization of generic cabling systems according to EN 50173; ISO/IEC 11801. Ideal for indoor applications in Class E up to 1GbE over IEEE 802.3ab and PoE/PoE+/PoE++ protocols. Electrical characteristics exceed Category 6 requirements.
Reference standards
Data transmission cables of Category 6 according to ISO/IEC 11801-1/2:2017; IEC 61156-5 Ed.2.1; EN 50173-1/2:2018; ANSI/TIA-568.2-D.
Construction characteristics
Inner conductors - material/diameter
Solid bare copper/AWG 23/1(0,57 mm)
Insulation - material/diameter
PEmax diam. 1,14 mm
Cable diameter
7,3 mm
Overall shield
Al/PET tape + CuSn drain wire
Outer jacket - material/color
LSZH/Orange RAL 2003
Lead-free
Yes
Cable weight
53 kg/Km
ELECTRICAL CHARACTERISTICS ACCORDING TO FREQUENCY
Freq
Attenuation
NEXT
PS-NEXT
ACR
PS-ACR
ACR-F
PS-ACR-F
RL
MHz
dB/100m
dB
dB
dB@100m
dB@100m
dB@100m
dB@100m
dB
max.*
Tip.
min.*
Typ.
min.*
Tip.
min.*
Typ.
min.*
Typ.
min.*
Typ.
min.*
Typ.
min.*
Typ.
1
2.1
1.7
66
90
64
87
64
88.3
62
85.3
66
86
64
77
-
26
10
6
5.2
59
80
57
73
53
74.8
51
67.8
50
68
47
61
25
32
31.25
10.7
9.4
52
72
50
66
41
62.6
39
56.6
40
60
37
51
23.6
33
62.5
15.5
13.5
47
67
45
61
32
53.5
30
47.5
34
54
31
46
21.5
31
100
19.9
17.1
44
65
42
57
24
47.9
22
39.9
30
48
27
41
20.1
30
155
25.3
21.6
41
62
39
54
16
40.4
14
32.4
26
45
23
37
18.8
28
200
29.1
24.7
40
60
38
53
11
35.3
9
28.3
24
41
21
35
18
27
250
33
27.6
38
57
36
52
5
29.4
3
24.4
22
36
19
30
17.3
26
300
-
31.2
-
55
-
51
-
23.8
-
19.8
-
35
-
29
-
25
400
-
36
-
53
-
49
-
17
-
13
-
32
-
26
-
23
500
-
40.7
-
51
-
48
-
10.3
-
7.3
-
30
-
24
-
21
according to EN 50288-5-1(2013); IEC 61156-5(2012)